How do you wire the iR-DM16-N?
Why does the iR-DQ16-N have two UV/UG terminals?
Both the iR-DQ16-N and iR-DQ16-P have an extra set of UV & UG terminals that will allow you to supply power to another module. This method is illustrated within the example below:
How many modules can I connect to one iR-ETN?
Note: Modules cannot be removed or connected to the device during runtime. This known as a “Hot-Swap” and is not supported by the iR-ETN, iR-ETN40R, or cMT-CTRL01.
Does each module need its own power source?
Yes, each module requires its own external power source.
How can I determine why the “ERR” light is on?
How can I determine why the “ERR” light is on? If you are using an iR-ETN or iR-ETN40R, you can monitor the I/O modules using EasyRemote IO via the following method: 1. Open EasyRemote IO and select the “Scan” button: 2. Within the following popup, click “Scan”: 3. When the scan is finished click “Ok” […]
Where can I find information about I/O parameters?
The user manual that corresponds with the specified I/O module will contain a detailed description of the parameters found within EasyRemote IO. The aforementioned user manuals can be found within this post: Click Here In addition, we have created a table that contains all available project parameters and their description: Click Here“
What is EasyRemote IO?
EasyRemote IO is an application that will allow you to configure the parameters of an iR-ETN or iR-ETN40R and connected IO modules. For more information, please see the EasyRemote IO user manual.
Can I use Weintek’s I/O without Codesys?
Yes, Weintek’s iR series remote I/O can be used with any device that supports the protocols mentioned above. However, please ensure that you choose the correct coupler for your application.