Can Weintek HMIs use Codesys Visualization?
No. Weintek has been developing HMI software for 30+ years and we believe that we have the best HMI software available. Our EasyBuilder Pro software is Free and extensive in its capabilities.
How much memory can be used in a Weintek’s Codesys project?
Here are the specs for reference: Data, Input, Output, Memory, Code Retain area 3 MB (Data persists after reboots)(Data is saved every 1 minute)Persistent area 16 KB (Data persists after downloads) (Data is saved every 1 minute) 16 KB File system 8 MB Note: 3MB for “Data, Input, Output, Memory, Code” is the max. size […]
How much memory can be used in a Weintek’s Codesys project?
Here are some base level measurements for comparison:
What libraries does Weintek’s Codesys support?
“Weintek’s built-in Codesys is compatible with wide range of built-in libraries. However, certain libraries that require OS support are not compatible with the device runtime. The libraries within the table below are compatible with Weintek’s built-in Codesys. Libraries that do not require OS support are also compatible with Weintek’s built-in Codesys.; e.g. OSCAT Basic, Util […]
What features cannot be used with Weintek’s Codesys runtime?
OPC UA features Network Variable List Alarm Configuration (Alarm Manager) Redundancy Configuration CODESYS TargetVisu CODESYS WebVisu CODESYS HMI SoftMotion CODESYS IIoT Libraries SL CODESYS OPC UA Client SL CODESYS OPC UA Server SL CODESYS Safety for EtherCAT Safety Module SL Other add-ons Trying to install other licenses from the CODESYS website will not work.
How many devices can Weintek’s Codesys communicate with?
Modbus TCP/IP 32 devices EtherCAT 65,535 devices CANopen 126 devices EtherNet/IP 32 devices PROFINET 32 devices
What communication drivers should I use within Codesys?
We recommend that you use device drivers included with Weintek’s Codesys package: Device Version CANbus 3.5.15.0 CANopen manager 3.5.15.0 Ethernet adapter (added under Ethernet IP Scanner) 3.5.15.0 Ethernet IP Scanner 3.5.15.50 Modbus TCP maste 3.5.15.0 EtherCAT master 3.5.12.0 PROFINET master 3.5.13.0 Note: You may need to select “Display all versions” within the “Add Device” dialog […]
Can Weintek’s Codesys communicate with a third-party device?
Certainly! You may use any of the protocols mentioned above to communicate with an external device of your choice.
What protocols does Weintek’s Codesys support?
Currently Weintek’s built-in Codesys supports the following protocols: Modbus TCP/IP (master) EtherCAT (master) CANopen (master) Prerequisite: CANopen is only available on Weintek CMT-X HMIs that are equipped with a CANBus port. EtherNet/IP (master) PROFINET (master) Note: Weintek’s Codesys cannot act as a Modbus TCP Slave by adding a single Modbus Slave device in the device […]
How do I connect to Weintek’s Codesys?
Codesys has complete control over LAN-1, please make sure that your PC is connected to LAN-1 or that you have “Codesys Login” enabled on the HMI. While “Codesys Login” is enabled, you can connect to the HMI and Codesys using LAN-2. To enable Codesys Login, please read this post: How to enable Codesys login Once […]